Introduction
Time-saver at your service for cable diagnostics:
Technical data of TV60 | |
Input voltage |
220V AC±10%, 50Hz |
Output voltage |
|
DAC |
0-60 kV(peak)/0-42.4kV (rms) |
Precision |
±1% |
Resolution |
0.1kV |
Frequency range |
20Hz~500Hz |
Capacity range |
1 nF ... 10 μF at 30 kVpeak |
1 nF ... 4.25 μF at 60 kVpeak | |
PD sensitivity range |
2 pC … 100 nC (acc. to IEC60270) |
Resolution |
±1pC |
System noise level |
< 20 pC at 60 kV(peak) |
PD localisation |
|
Measuring range |
0 … 20,000m |
Propagation velocity |
5 … 120m/µs |
Sampling rate |
200 MHz |
Bandwidth |
150kHz ~ 45MHz, automatic adjustment |
Precision |
1% of the cable length |
Resolution |
± 1pC / ± 0.1m |
TD(Tan Delta) test |
|
Measuring range |
0.1% ~ 10%, automatic adjustment |
TDR joint localisation in
calibration mode
|
Integrated |
Software |
User selectable graphical interface, online “live” PD mapping |
integrated measurement database, comprehensive viewing | |
processing, analysing and reporting of measurement data | |
Temperature |
|
Operation |
-20 °C … 55 °C |
Storage |
-30 °C … 70 ° |
Relative humidity |
93 % at 30 °C (non-condensing) |
Weight |
100 kg(net) |
Dimensions |
Ø 690 x H 1000 mm |