Introduction
Features
Parameters
HIGH VOLTAGE PART TECHNICAL DATA | |
HV DC source | 0-32 kV DC test (DC hipot) |
60 mA nominal continuous current at 32 kV | |
Breakdown detection | 0-32 kV |
Standard surge levels |
0… 8 / 0 … 16 / 0 … 32 kV
2,432 / 2,432 / 2,432 J
|
Surge rate | Adjustable 3-10 sec, and single shot |
Built-in prelocation | TDR,ARM ,ICE,DECAY |
Sheath testing |
0-32kV |
Communication ways |
Wi-Fi 2.4G |
Control |
Auto Go APP(Android version) |
Grounding detect range |
≥0.5Ω |
Grounding detect set |
2~10Ω adjustable |
Grounding detect accuracy |
Better than 0.2Ω |
Step voltage detect range |
0.5~200V(peak) |
Step voltage detect set |
0.5~42V(30VAC) |
Step voltage detect accuracy |
Better than 0.2V |
Operating temperature | -20 ~ +45℃ |
Storage temperature | -40 ~ +60℃ |
Weight | 180kg |
Mains input supply | 220V AC,50/60 Hz,2kW |
Dimensions (L x W x H) | 900*650*703 mm |
Protection class | IP43 |
RADAR AND CONTROL UNIT TECHNICAL DATA | |
TDR setup | Physically and functionally integrated |
Contorl | Wireless tablet computer and Emergency Stop Box |
Display | 11.5'' |
Pulse generation | Bipolar |
Pulse amplitude | 50v |
Pulse width | 50ns ~10μs |
Measuring range | 0 m-100 km, at VOP = 80 m/µs |
ProRange | 0 -40dB |
Resolution | 0.1m(at 172m/μs) |
Accuracy |
0.10% |
Gain level |
6 |
Data rate | 200MHz |
Velocity of propagation | 100-300m/μs |
Multishot support | Yes, 5 HV fault traces, |
Waveform storage capacity | Unlimited |